BR Series, 250A-1600A

A Flexible, Safe, and Reliable Low Voltage Power Distribution Solution

With the brand vision “Smarter, Greener, Together,” Delta has utilized its industry-leading power electronics technology to develop the Busway BR Series for data center applications. Different from a conventional power cable system or sandwich busway solutions, Delta has adopted epoxy cast resin technology to significantly increase IP protection level, safety, and reliability. Delta’s solution is ideal for use in a variety of industries and climate conditions. The superior electrical and mechanical characteristics of resin minimize the Busway BR Series’ dimensions and simplify its structure. The Busway BR Series also has an extended product life cycle, increased reusability, and achieves significant energy savings for customers.

Customer Value 

The Busway BR Series features:

  1. Continuous plug-in core technologies available for expansion and power distribution. Data centers can use them
    freely
  2. Ultra safe solution that satisfies the requirements of data centers
  3. Conforms to different standards, depending on market or customer needs, such as IEC, CNS and GB
  4. Space-saving and weight-saving solution that overcomes space and loading problems of the data center.
  5. Highly integrated composite materials that significantly reduce EMC and protect precision devices in the data center,
    and are safe for human health.

Product Advantages  

Busway Body

  1. Wide power ratings ranging from 250A to 1600A
  2. Up to 200% neutral
  3. Highly integrated cast resin technology with epoxy inside
  4. Pole locations can be reserved or customer can choose the continuous plug-in units upon request
  5. Numerous standard lengths are available, such as 1M, 2M, 3M, 4M, 5M, 6M
  6. Length can be customized upon customer request
  7. IP protection level up to IP54

Plug-in Unit

  1. Easy expansion, plug and play and hot swappable without interruption
  2. No special tools required for installation
  3. Users can use a single module or multiple modules in parallel
  4. Highly customized plug-in units work with power meters and circuit breakers from major vendors
  5. Monitoring module is available for options

Conductor Material

  1. Users can select copper or aluminum types as needed
  2. Conductivity of copper conductor is above 99.9%
  3. Copper conductors are entirely tin plated for optimum conductivity and contact reliability

Resin Material

  1. Uses epoxy cast resin technology that is highly insulating (Class F 155℃ ) to enhance safety and reliability
  2. Fire resistance, waterproof, insulation rating, resistance to chemical and corrosion level compliant with industrial standards
  3. Guaranteed high reliability even in harsh environmental conditions (up to IP54)

Busway for Data Center Applications

With the recent wave of Big Data and IoT, data centers are responsible for more computing, communication and storage functions. In addition to the increase of their scope, the power density of a single rack cabinet has gradually increased. Effective space utilization is a great challenge for data center construction.

The Delta Cast Resin Busway System BR Series is exclusive for data center applications. Thanks to the epoxy insulation technology, it has a compact structure and size, as well as low EMC that allows it to overcome space limitations in server rooms. Data center designers can easily do wiring construction close to data cables without fear of an impact on their health due to low electromagnetic radiation.

In addition, the plug-in unit can be customized per customers’ requirement. It is flexible for use with different power supply systems of server racks. The plug-in unit also applies the flexible “Continuous Plug-In” core technology and is hot swappable. Therefore, it is not constrained by data center space. Customers can carry out expansion or distribution anywhere, which is very flexible.

Safe

The IP55 protection level provides water resistance and is dustproof. The busway remains highly reliable even in harsh environmental conditions, such as high humidity and dripping water. Delta has considered all aspects of the structure design.

  1. Installation: Attentive foolproof designs are available for every installation step
  2. Operation: Tool-less design for users to easily install plug-in units
  3. Compliant with IEC 61439

Reliable 

The busway structure is an Aluminum housing. The busway adopts epoxy cast technology, which is filled and molded into one piece. Its advantages include:

  1. Minimizes risk from the stronger structure during lifting and assembly on data center sites
  2. Shield technology ensures optimum sequencing of the conductor. The integrated composite materials reduce EMC significantly and mitigate the interference to precision devices
  3. No maintenance is required

Efficient

The product design and installation uses many plug-ins and modular design concepts and is easy-to-use during the installation, operation and expansion phases.

Benefits of the continuous plug-in and modular design are:

  1. Unconstrained by space or location, the busway can be designed effectively and installed without professional technicians
  2. The plug-in unit adopts a modular design that can be expanded simply and quickly
  3. Customers can save time on waiting for materials if there is any change in design
  4. can save time and costs on installation, expansion, and alteration

Specifications

Busway Rating : 250A
Model : BRC02
Rated voltage (AC/DC) : 1000V
Rated current : 250A
Frequency : 50/60 Hz
Resistance* : R20 : 213.0 μΩ/m; R85 : 267.4 μΩ/m; X50 : 138.1 μΩ/m; X60 : 165.7 μΩ/m
Impedance* : Z50 : 301.0 μΩ/m; Z60 : 314.6 μΩ/m

Conductor cross-section area : L1,L2,L3 : 72.5 mm2; N (100%) : 72.5 mm2; G (Internal) : 72.5 mm2
Busway Dimensions (h x w) : 58 x 117 mm

 
 

Busway Rating : 400A
Model : BRC04
Rated voltage (AC/DC) : 1000V
Rated current : 400A
Frequency : 50/60 Hz
Resistance* : R20 : 178.0 μΩ/m; R85 : 223.5 μΩ/m; X50 : 129.5 μΩ/m; X60 : 155.4 μΩ/m
Impedance* : Z50 : 258.3 μΩ/m; Z60 : 272.0 μΩ/m
Conductor cross-section area : L1,L2,L3 : 100 mm2; N (100%) : 100 mm2; G (Internal) : 50 mm2
Busway Dimensions (h x w) : 58 x 117 mm

 
 

Busway Rating : 600A
Model : BRC06
Rated voltage (AC/DC) : 1000V
Rated current : 600A
Frequency : 50/60 Hz
Resistance* : R20 : 106.3 μΩ/m; R85 : 133.5 μΩ/m; X50 : 112.3 μΩ/m; X60 : 134.8 μΩ/m
Impedance* : Z50 : 174.5 μΩ/m; Z60 : 189.7 μΩ/m
Conductor cross-section area : L1,L2,L3 : 145 mm2; N (100%) : 145 mm2; G (Internal) : 72.5 mm2
Busway Dimensions (h x w) : 58 x 117 mm

 
 

Busway Rating : 800A
Model : BRC08
Rated voltage (AC/DC) : 1000V
Rated current : 800A
Frequency : 50/60 Hz
Resistance* : R20 : 68.7 μΩ/m; R85 : 86.2 μΩ/m; X50 : 79.9 μΩ/m; X60 : 95.9 μΩ/m
Impedance* : Z50 : 117.5 μΩ/m; Z60 : 128.9 μΩ/m
Conductor cross-section area : L1,L2,L3 : 232 mm2; N (100%) : 232 mm2; G (Internal) : 116 mm2
Busway Dimensions (h x w) : 73 x 117 mm

 
 

Busway Rating : 1000A
Model : BRC10
Rated voltage (AC/DC) : 1000V
Rated current : 1000A
Frequency : 50/60 Hz
Resistance* : R20 : 50.2 μΩ/m; R85 :63.0 μΩ/m; X50 : 57.3 μΩ/m; X60 : 68.8 μΩ/m
Impedance* : Z50 : 85.2 μΩ/m; Z60 : 93.3 μΩ/m
Conductor cross-section area : L1,L2,L3 : 307.4 mm2; N (100%) : 307.4 mm2; G (Internal) : 153.7 mm2
Busway Dimensions (h x w) : 86 x 117 mm

 
 

Busway Rating : 1250A
Model : BRC12
Rated voltage (AC/DC) : 1000V
Rated current : 1250A
Frequency : 50/60 Hz
Resistance* : R20 : 34.7 μΩ/m; R85 :43.5 μΩ/m; X50 : 42.3 μΩ/m; X60 : 50.8 μΩ/m
Impedance* : Z50 : 60.7 μΩ/m; Z60 : 66.9 μΩ/m
Conductor cross-section area : L1,L2,L3 : 464 mm2; N (100%) : 464 mm2; G (Internal) : 232 mm2
Busway Dimensions (h x w) : 113 x 117 mm

 
 

Busway Rating : 1600A
Model : BRC16
Rated voltage (AC/DC) : 1000V
Rated current : 1600A
Frequency : 50/60 Hz
Resistance* : R20 : 23.0 μΩ/m; R85 :28.9 μΩ/m; X50 : 28.0 μΩ/m; X60 : 33.6 μΩ/m
Impedance* : Z50 : 40.2 μΩ/m; Z60 : 44.3 μΩ/m
Conductor cross-section area : L1,L2,L3 : 696 mm2; N (100%) : 696 mm2; G (Internal) : 348 mm2
Busway Dimensions (h x w) : 153 x 117 mm

 

 
 

* Impedance values are for busway operating at 20/85℃ temperature.

Plug-in Unit (Rv Type)

 

Rating : 16A
Model : Rv-A3P16
Dimensions (H x D x W) : 275 x 165 x 100 mm
IP Rating : IP42
Weight : 3 kg

 
 

Rating : 32A
Model : Rv-A3P32
Dimensions (H x D x W) : 275 x 165 x 100 mm
IP Rating : IP42
Weight : 3 kg

 
 

Rating : 63A
Model : Rv-A3P63
Dimensions (H x D x W) : 275 x 165 x 100 mm
IP Rating : IP42
Weight : 3 kg

 
 

Rating : 125A
Model : Rv-A3P125
Dimensions (H x D x W) : 275 x 165 x 200 mm
IP Rating : IP42
Weight : 12 kg

 
 

Rating : 250A
Model : Rv-A3P250
Dimensions (H x D x W) : 275 x 165 x 300 mm
IP Rating : IP42
Weight : 20 kg

 
 

Rating : 400A
Model : Rv-A3P400
Dimensions (H x D x W) : 275 x 165 x 300 mm
IP Rating : IP42
Weight : 26 kg

Plug-in Unit (Rh Type)

 Rating : 16A

Model : Rh-A3P16
Dimensions (H x D x W) : 250 x 185 x 100 mm
IP Rating : IP42
Weight : 3 kg

 
 

Rating : 32A
Model : Rh-A3P32
Dimensions (H x D x W) : 250 x 185 x 100 mm
IP Rating : IP42
Weight : 3 kg

 
 

Rating :63A
Model : Rh-A3P63
Dimensions (H x D x W) : 250 x 185 x 100 mm
IP Rating : IP42
Weight : 3 kg

 
 

Rating : 125A
Model : Rh-A3P125
Dimensions (H x D x W) : 250 x 185 x 200 mm
IP Rating : IP42
Weight : 12 kg

 
 

Rating : 250A
Model : Rh-A3P250
Dimensions (H x D x W) : 250 x 185 x 300 mm
IP Rating : IP42
Weight : 20 kg

 
 

Rating : 400A
Model : Rh-A3P400
Dimensions (H x D x W) : 250 x 185 x 300 mm
IP Rating : IP42
Weight : 26 kg

 
 

End Feed Box

Rating : 250A
Catalogue Number : Rt-3P250
Dimensions (W x H x D) : 160 x 300 x 430 mm
Color : RAL7043
IP Rating : IP42
Weight : 15 kg

 
 

Rating : 400A
Catalogue number : Rt-3P400
Dimensions (W x H x D) : 160 x 300 x 430 mm
Color : RAL7043
IP Rating : IP42
Weight : 15 kg

 
 

Rating : 630A
Catalogue number : Rt-3P630
Dimensions (W x H x D) : 160 x 300 x 430 mm
Color : RAL7043
IP Rating : IP42
Weight : 17 kg

 
 

Rating : 1250A
Catalogue number : Rt-3P1250
Dimensions (W x H x D) : 250 x 300 x 430 mm
Color : RAL7043
IP Rating : IP42
Weight : 21 kg

 
 

Rating : 1600A
Catalogue number : Rt-3P1600
Dimensions (W x H x D) : 250 x 300 x 430 mm
Color : RAL7043
IP Rating : IP42
Weight : 28 kg