Power Distribution Unit

For power distribution requirements of medium to large data centers, Delta’s Power Distribution Unit (PDU) provides an optimal solution. The space-saving PDU is easy to move and adapt to future reconfigurations of the data center. The PDU offers superior power protection and monitoring, and the flexibility & scalability to match your actual power distribution requirements. Not only does it improve availability, it reduces the cost of your initial investment.

Convenience 

  1. Configurable circuit breaker panel
  2. LCD display supporting multiple languages
  3. Recording more than 500 event logs
  4. Monitoring the current of each branch circuit breaker
  5. Built-in RS232 interface for remote monitoring
  6. Six built-in six contact closure outputs
  7. Two built-in SNMP interfaces increasing availability

Safety  

  1. Local and remote emergency power off functions
  2. Current unbalance and phase sequence error alarm
  3. Optional K-factor isolation transformer enhancing safety and reduces harmonics
  4. Optional lightning surge protection module

Availability

  1. Easy to relocate, reducing investment costs
  2. Two built-in sets of panelboards with 42 poles each
  3. Optional transformers for different output voltages

Specifications

Model

PDU 80 / PDU 125

 
 

Capacity
PDU 80 : 80kVA
PDU 125 : 125 kVA

 
 

Input
Rated voltage : 220/380 Vac, 3 phase 3 wire+ ground, or 3 phase 4 wire+ ground
Voltage tolerance range : ±15%
Frequency : 50 / 60 Hz ±5% (Automatic detection)

 
 

Output
Rated voltage : 220/380 Vac, 3 phase 4 wire+ ground,
Total switching capacity : Based on actual product specifications
Switchboard type : Two groups of switchboards and 42 poles each

Shunt switch type :
Hot-swap switch capacity: 15 / 20 / 30A,
Optional: 1/2/3 pole

 
 

Transformer
Input-Output Type : Δ-Y
Efficiency : 97.5% (Full-load)

 
 

LCD Display
System : Temperature, ground current, System overheat alarm, V-Loss Alarm, Voltage Imbalance Alarm, Ground Fault Alarm

 
 

Blue light 4.9” graphic interface
Input
Phase voltage, line voltage, phase current, line current, load(%), iTHD, total kVA, total kW, total kWh, Over voltage/over current alarm, under-voltage/nder current alarm, Over line current alarm, iTHD abnormal alarm

Total output
Phase voltage, line voltage, phase current, line current, frequency, neutral current, load(%), kVA, kW, kWh, power factor, VTHD, iTHD, Over voltage/over current alarm, under-voltage/under current alarm, Over line current alarm, iTHD abnormal alarm, VTHD abnormal alarm, power factor abnormal alarm

Output shunt plate
Phase current, kVA, kW, kWh, load (%), iTHD, power factor, line current, over current alarm, under current alarm, Over line current alarm, iTHD abnormal alarm, power factor abnormal alarm

Output shunt
Current, load (%), over current alarm, under current alarm

Temperature
Environment (instant and alarm), transformers (two stage-alarm)

 
 

Regulatory Compliance
Environment : CE
Electromagnetic interference : EN55022

 
 

Communication interface : RS232 x 1, dry contact x 6, SNMP slot x 2

 
 

Optional accessories : Lightning protector

 
 

Size (width, depth, height) : 600 x 1090 x 2000mm standard 19” cabinet

 
 

Weight
Excluding transformer: 225kg, including H transformer: 80kVA: 525 kg, 125 kVA: 630 kg

 
 