Availability
Flexibility
Low Total Cost of Ownership
INX Series 1/2/3 kVA UPS – Standard Runtime Models & Extended Runtime Models (6A) (Leaflet)
INX Series 1/2/3 kVA UPS – Extended Runtime Models (16A) (Leaflet)
INX Series 1/2/3 kVA UPS – Standard Runtime Models & Extended Runtime Models (6A) (User Manual)
INX Series 123 kVA UPS – Extended Runtime Models (16A) (User Manual)
Model
INX-1K / INX-2K / INX-3K
Power Rating
1K: 1kVA/0.8kW
2K: 2kVA/1.6kW
3K: 3kVA/2.4kW
Input
Nominal Voltage: 230 Vac
Voltage range: 110 ~ 300 Vac*
Frequency: 40 ~ 70 Hz
Power Factor: > 0.99 @ nominal voltage (input voltage)
Output
Power Factor: 0.8
Voltage: 200**/208**/220/230/240 Vac
Voltage Regulation: ± 1% (Battery mode)
Frequency: 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Voltage Harmonic Distortion:
≤ 3% (linear load)
≤ 6% (non-linear load)
Overload Capability:
< 105%: Continuous
105% ~ 110%: 10 minutes
110% ~ 130%: 1 minute
130%: 3 seconds
Crest Factor: 3:1
Receptacle
Standard Runtime Model
1K: India socket x 3
2K: India socket x 4
3K: India socket x 4 + Terminal block x 1
Extended Runtime Model (6A)
1K: India socket x 2
2K: India socket x 2 + Terminal block x 1
3K: India socket x 2 + Terminal block x 1
Efficiency
Online Mode
1K: 88%
2K: 89%
3K: 90%
Battery Voltage
Standard Runtime Model
1K: 24 Vdc
2K: 48 Vdc
3K: 72 Vdc
Extended Runtime Model (6A)
1K: 36 Vdc
2K: 72 Vdc
3K: 72 Vdc
Charger Current
Standard Runtime Model: 1A
Extended Runtime Model (6A): 1/2/4/6A
Audible Noise: <50 dB @ 1 meter
Display: LCD
Communication Interfaces: Mini Slot x 1, RS-232 Port x 1, USB Port x 1
Dimensions
Standard Runtime Model(W x D x H):
1K: 282 x 145 x 220 mm
2K: 504 x 145 x 220 mm
3K: 421 x 190 x 318 mm
Extended Runtime Model (6A) (W x D x H):
1K: 282 x 145 x 220 mm
2K: 397 x 145 x 220 mm
3K: 397 x 145 x 220 mm
Weight
Standard Runtime Model:
1K: 9 kg
2K: 16.5 kg
3K: 25 kg
Extended Runtime Model (6A):
1K: 4.4 kg
2K: 7.3 kg
3K: 7.8 kg
Environment
Operating Temperature: 0 ~ 40°C
Relative Humidity: 20% ~ 90% (non-condensing)
* At 110 ~ 160 Vac, linear de-rating between 60 ~ 100% load is required.
** De-rate capacity to 80% when the output voltage is adjusted to 200 Vac or 208 Vac.
Please refer to the rating label for the safety rating.
All specifications are subject to change without prior notice.
Extended Runtime Models (16A)
Model
INX-1K / INX-2K / INX-3K
Power Rating
1K: 1kVA/0.9kW
2K: 2kVA/1.8kW
3K: 3kVA/2.7kW
Input
Nominal Voltage: 230 Vac
Voltage range: 110 ~ 300 Vac*
Frequency: 40 ~ 70 Hz
Power Factor: > 0.99 @ nominal voltage (input voltage)
Output
Power Factor: 0.9
Voltage: 200**/208**/220/230/240 Vac
Voltage Regulation: ± 1% (Battery mode)
Frequency: 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Voltage Harmonic Distortion:
≤ 2% (linear load)
≤ 4% (non-linear load)
Overload Capability:
100% ~ 110%: continuous
110% ~ 130%: 2 minutes
130% ~ 140%: 30 seconds
>140%: 1.5 seconds
Crest Factor: 3:1
Receptacle:
1K: Indian socket x 3
2K: Indian socket x 3
3K: Indian socket x 4
Efficiency
Online Mode:
1K: 89%
2K: 90%
3K: 91%
Battery Voltage:
1K: 36 Vdc
2K: 72 Vdc
3K: 72 Vdc
Charge Current: 1/2/4/6/8/10/12/14/16A (adjustable via LCD display)
Audible Noise: < 50 dB @ 1 meter
Display: LCD
Communication Interfaces: Mini Slot x 1, RS-232 Port x 1, USB Port x 1, EPO x 1
Dimensions (W x D x H):
1K: 397 x 145 x 220 mm
2K: 397 x 145 x 220 mm
3K: 421 x 190 x 318 mm
Weight:
1K: 5.5 kg
2K: 6.4 kg
3K: 13.1 kg
Environment
Operating Temperature: 0 ~ 40°C
Relative Humidity: 20% ~ 95% (non-condensing)
* At 110 ~ 160 Vac, linear de-rating between 60 ~ 100% load is required.
** De-rate capacity to 80% when the output voltage is adjusted to 200 Vac or 208 Vac.
Please refer to the rating label for the safety rating.
All specifications are subject to change without prior notice.