N Series Single Phase 1/2/3 kVA

High-performance power protection with greater energy savings

TThe Amplon N series is a true online double-conversion UPS that can provide your critical equipment with reliable, stable sine wave power. It features significant advantages, including an output power factor of 0.9 and up to 93% AC-AC efficiency for greater energy savings. The Amplon N series provides a safe power supply guaranteed for mission critical applications such as work stations, POS, ATMs, and more.

Availability 

  1. True online double-conversion topology and zero transfer time to battery ensure high reliability.
  2. Advanced DSP (Digital Signal Processor) controller for fast computation capability and a simplified control circuit for enhanced stability.
  3. Wide input voltage range allows the UPS to work in harsh electrical environments.
  4. Generator compatibility ensures continuous and reliable power

Green with Low TCO  

  1. High input power factor (> 0.99) and low input harmonic distortion (iTHD < 3%) save upstream investment.
  2. Output power factor up to 0.9 presents a stronger load capacity.
  3. AC-AC efficiency up to 93% and high efficiency of 91% at 50% load results in marked energy cost savings.
  4. Compact design saves more space for critical equipment.

Intelligent Management

  1. Excellent local communications through LCD display.
  2. Intelligent battery management maximizes battery performance and sustains battery life.
  3. Mini slot and USB port enhance monitoring and manageability.

Specifications

Model

N-1K / N-2K / N-3K

Power Rating
N-1K : 1kVA/0.9kW
N-2K : 2kVA/1.8kW
N-3K : 3kVA/2.7kW

Input
Nominal Voltage : 220/230/240 Vac
Voltage Range : 175 ~ 280 Vac (full load), 80~175 Vac (50%-100% load)
Frequency : 50/60 Hz ± 10 Hz
Power Factor : > 0.99 (full load)
Current Harmonic Distortion : < 3%

Output
Power Factor : 0.9
Voltage : 220/230/240 Vac
Frequency :50/60 ± 0.05 Hz
Voltage Harmonic Distortion : < 3% (linear load)
Overload Capability
< 105%: continuous
105 ~ 125%: 1 minutes
125 ~ 150%: 30 seconds
Crest Factor : 3:1

Receptacle
N-1K : IEC C13 x 4
N-2K/N-3K : IEC C13 x 6, C19 x 1

Efficiency
AC-AC
N-1K : 91%
N-2K/N-3K : Up to 93%

Battery
Battery Voltage
N-1K : 24 Vdc
N-2K : 48 Vdc
N-3K : 72 Vdc
Typical Backup Time : 4.5 min.(full load), 13 min.(half load)
Recharge Time : 3hrs to 90%
Charge Current : 1.5A

Audible Noise
N-1K : < 43 dBA
N-2K/N-3K : < 48 dBA

Display : LCD panel

Interface : MINI Slot x 1, USB Port x 1

Comformance
Safety & EM : CCE/RCM/EN62040-1/EN62040-2 Category C2

Physical
Dimensions (WxDxH)
N-1K : 145 x 320 x 225 mm
N-2K/N-3K : 190 x 390 x 325 mm

Weight
N-1K : 9 kg
N-2K : 18.6 kg
N-3K : 24.4 kg

Environment
Operating Temperature : 0 ~ 40ºC
Relative Humidity : 5 ~ 95% (non-condensing)