Availability
Flexibility
Low Total Cost of Ownership
Model
DPS-160K / DPS-200K / DPS-300K / DPS-400K / DPS-500K
Power Rating
DPS-160K : 160kVA/144kW
DPS-200K : 200kVA/180kW
DPS-300K : 300kVA/270kW
DPS-400K : 400kVA/360kW
DPS-500K : 500kVA/450kW
Input
Nominal Voltage : 380/220, 400/230, 415/240 Vac (3 phase, 4-wire + G)
Voltage Range : 324~477 Vac (full load), 242~324 Vac (70%~100% load)
Current Harmonic Distortion : < 3% * Power Factor : > 0.99
Frequency : 45~65Hz
Output
Voltage : 380/220, 400/230, 415/240 Vac (3 phase, 4-wire + G)
Output Power Factor : 0.9 (standard); 1 (optional) **
Voltage Harmonic Distortion : ≤ 1.5% (linear load); < 1% (linear load) **
Voltage Regulation : ± 1% (static)
Frequency :50/60 ± 0.05 Hz
Overload Capability : ≤ 125%: 10 minutes; ≤ 150%: 1 minute
Display : Mimic LCD supports multi-language and LED indicators
Communication Interfaces
Standard : RS232 x 1, Smart slot x 2, Output dry contact x 6, Input dry contact x 7, (Input dry contact (two sets), REPO x 1, External battery cabinet status detection x 1, External battery cabinet temperature detection x 4), Parallel port x 2, USB port x 1
Conformance
Safety & EMC : CE,RCM
Other Features
Parallel Redundancy : Up to 8 units
Emergency Power Off : Local and remote
Event Log : 500 records
Efficiency
AC-AC : Up to 96%
ECO Mode : Up to 99%
Environment
Operating Temperature : 0 ~ 40°C
Relative Humidity : 0 ~ 95% (non-condensing)
Audible Noise
DPS-160K/200K : <70 dBA
DPS-300K/400K : <73 dBA
DPS-500K : <76 dBA
IP Protection : IP20
Physical
Dimensions(WxDxH)
DPS-160K/200K : 850 x 865 x 1950 mm
DPS-300K/400K/500K : 1600 x 865 x 1950 mm
Weight
DPS-160K/200K : 697 kg
DPS-300K/400K : 1200 kg
DPS-500K : 1220 kg
* When input harmonic distortion is less than 1%.
** Available in South East Asia, Australia and New Zealand.
All specifications are subject to change without prior notice.R-1K / R-2K / R-3K
Power Rating
R-1K : 1kVA/0.9kW
R-2K : 2kVA/1.8kW
R-3K : 3kVA/2.7kW
Input
Nominal Voltage : 200*/208*/220/230/240 Vac
Voltage Range
175 ~ 280 Vac (full load)
80 ~ 175 Vac (50% ~ 100% load)
Frequency : 50/60 Hz ± 10 Hz
Power Factor : > 0.99 (full load)
Current Harmonic Distortion : < 3%
Output
Power Factor : 0.9
Voltage : 200*/208*/220/230/240 Vac
Voltage Regulation : ± 1% (linear load)
Frequency : 50/60 Hz ± 0.05 Hz
Overload Capability
< 105%: Continuous
105 ~ 125%: 1 minute
125 ~ 150%: 30 seconds
Receptacle
R-1K : IEC C13 x 4
R-2K : IEC C13 x 2, IEC C19 x 1
R-3K : IEC C13 x 2, IEC C19 x 1
Efficiency
AC-AC
R-1K : 91%
R-2K/R-3K : Up to 93%
ECO Mode
R-1K : 95%
R-2K/R-3K : Up to 96%
Battery
Battery Voltage
R-1K : 24 Vdc
R-2K : 48 Vdc
R-3K : 72 Vdc
Charge Current : 4A (up to 8A with optional inbuilt charger)
Audible Noise**
R-1K : < 40 dB
R-2K/R-3K : < 43 dB
Display : LCD display and LED indicators
Communication Interfaces
Standard : Mini Slot x 1, RS-232 Port x 1, USB Port x 1
Conformance
Safety : CE
Physical
Dimensions (WxDxH)
R-1K : 440 x 335 x 88 mm
R-2K : 440 x 430 x 88 mm
R-3K : 440 x 430 x 88 mm
Weight
R-1K : 5.3 kg
R-2K : 9.0 kg
R-3K : 9.1 kg
Environment
Operating Temperature : 0 ~ 50°C***
Relative Humidity : 5 ~ 95% (non-condensing)
* When the UPS is de-rated to 90% of its capacity.
** If the UPS is running at <75% load and in room temperature.
*** When the operating temperature is at 40~50°C, the UPS will be de-rated to 80% of its capacity.