Availability & Flexibility
Efficiency & Reliability
Manageability
Model
RT-5K – Power Rating : 5kVA / 5kW
RT-6K – Power Rating : 6kVA / 6kW
RT-8K – Power Rating : 8kVA / 8kW
RT-10K – Power Rating : 10kVA / 10kW
RT-15K3P – Power Rating : 15kVA / 15kW
RT-20K3P – Power Rating : 20kVA / 20kW
Input
Voltage Range – RT-5/6/8/10K :
100 ~ 280V (Single phase, 2-wire + G)
100 ~ 175V with linear de-rating 50 ~ 100%
Voltage Range – RT-15/20K3P :
138 ~ 485V (Three phase, 4-wire + G)
138 ~ 305V with linear de-rating 40 ~ 100%
Frequency : 40 ~ 70 Hz
Power Factor : > 0.99 (full load)
iTHD : < 3%
Input connection – RT-5/6/8/10K : Input terminal x 1
Input connection – RT-15/20K3P : Input terminal x 1, Bypass Input terminal x 1
Output
Power Factor : Unity
Voltage – RT-5/6/8/10K : 200, 208, 220, 230, 240 Vac (Single phase)
Voltage – RT-15/20K3P : 380/400/415 Vac (Three phase), or 220/230/240 Vac (Single phase)
Frequency : 50/60Hz ±0.05Hz
Voltage Harmonic Distortion : ≤ 2% (linear load)
Overload Capability – RT-5/6/8/10K :
≤ 105%: continuous
106 ~ 125%, 5 min.
126 ~ 150%, 1 min. >
150%: 500ms
Overload Capability – RT-15/20K3P :
≤ 105%: continuous
106 ~ 125%: 2 min.
126 ~ 150%: 30 sec
> 150%: 200ms
Receptacle
Standard Runtime Model
RT-5/6K : C13x6, C19x2, Terminal x 1, Load bank: C19x1
RT-8/10K : C13x6, C19x4, Terminal x 1, Load bank: C19x1
Extended Runtime Model
RT-5/6/8/10K : Terminal x 1, Load bank: Terminal x 1
RT-15/20K3P : Terminal x 1
Efficiency
AC-AC
RT-5/6/8/10K : Up to 95.5%
RT-15/20K3P : Up to 96.5%
ECO Mode : Up to 99%
Battery Voltage
Standard Runtime Model
RT-5/6K : 192 Vdc
RT-8/10K : 240 Vdc
Extended Runtime Model
RT-15/20K3P : ±144 Vdc*, ±192 ~ 264 Vdc
Charger Current
Standard Runtime Model
RT-5/6K : 1A (default)
RT-8/10K : 1.5A (default)
RT-15/20K3P : Up to 8A
Extended Runtime Model : Up to 8A
Typical Backup Time (Run Time Table)
Standard Runtime Model – 75% load
RT-5K : 7.5 min.
RT-6K : 5.5 min.
RT-8K : 9 min.
RT-10K : 6 min.
RT-15/20K3P : Depending on different configurations required by customers
Standard Runtime Model – Full load
RT-5K : 5 min.
RT-6K : 3 min.
RT-8K : 5 min.
RT-10K : 3.5 min.
Extended Runtime Model : Depending on different configurations required by customers
Audible Noise
RT-5/6K : 48 dB
RT-8/10K : 50 dB
RT-15/20K3P : 54 dB
Display : Graphical and multi-lingual LCD
Communication Interfaces : MINI Slot x 1, Parallel Port** x 2, USB Port x 1, RS232 Port*** x 1, RS485 Port x 1, REPO/ROO Port x 1, Dry Contact x 4
Dimensions (W x D x H)
Standard Runtime Model
RT-5/6K : 440 x 665 x 176 mm
RT-8/10K : 440 x 750 x 218 mm
Extended Runtime Model
RT-5/6K : 440 x 430 x 88.2 mm
RT-8/10K : 440 x 565 x 88.2 mm
RT-15/20K3P : 440 x 760 x 88.2 mm
Weight
Standard Runtime Model
RT-5/6K : 54 kg
RT-8/10K : 85.5 kg
Extended Runtime Model
RT-5/6K : 10.9 kg
RT-8/10K : 15.2 kg
RT-15K3P : 22.5 kg
RT-20K3P : 22.5 kg
Environment
Operating Temperature : 0 ~ 55° C****
Relative Humidity : 5 ~ 95% (non-condensing)
* De-rating to 70% load
** Only applicable to RT 5-10kVA Extended Runtime Model and RT 15/20kVA
*** Not applicable to RT 20kVA
**** When the operating temperature is at 40 ~ 55° C, the UPS will be de-rated to 75% of its capacity
All specifications are subject to change without prior notice.
Run Time
Standard Model
Extended Model