Ultron HPH Series UPS, Three Phase, 160/200 kVA

Highly reliable and efficient backup power for medium enterprise operations

The brand-new Ultron HPH series 160-200kVA is a true online double-conversion UPS offering the best-in-class combination of power performance and efficiency for medium data centers, pan-IT, and other mission critical applications. Thanks to Delta’s R&D expertise and excellent engineering capabilities, the Ultron HPH features up to 96.5% AC-AC efficiency, low iTHD < 3%, and high input power factor > 0.99 resulting in significant total cost of ownership (TCO) savings. Highlights of the highly reliable Ultron HPH series UPS design include key component redundancy and proactive battery health detection. With its combination of superior availability and power performance, the Ultron HPH 160-200kVA is the top choice for power protection of sustainable medium business operations.

Best-in-Class Power Performance and Efficiency 

  1. High AC-AC efficiency of up to 96.5% and ECO mode to 99% for significant energy cost savings
  2. Low harmonic pollution (iTHD < 3%) and high input power factor (> 0.99) reduces upstream investment costs

Assured Availability 

  1. Optional redundant controller supports dual CAN bus and ring connection for high system availability
  2. Proactive battery aging detection for high reliability
  3. Easy event log check via touch panel and firmware upgrade via USB port

Greater Flexibility

  1. Parallel expansion and redundancy up to 8 units, 1.6MVA of total power capacity
  2. Flexible battery configuration 30~46 pieces optimizes battery investment
  3. Supports either top or bottom cable entry in the single cabinet. The unique fixed symmetric terminal design avoids cable bending issues to enhance cable reliability

Superior Manageability  

  1. User-friendly 10” colored LCD with touch panel enables easy local UPS management
  2. Environment information such as security, water, fire and temperature can be integrated into the UPS for easy monitoring via the LCD of the UPS
  3. If the UPS is equiped with Delta’s battery management system, the battery information can be integrated into the UPS and monitored via LCD

Specifications

Model

HPH-160K / HPH-200K

 
 

Power Rating
HPH-160K : 160kVA* / 150kW
HPH-200K : 200kVA / 200kW

 
 

Input
Nominal Voltage : 220/380 Vac, 230/400 Vac , 240/415 Vac (3-phase, 4-wire + G)
Voltage Range : 176 ~ 276Vac (full load)
Current Harmonic Distortion : ≦ 3% **
Frequency : 40 ~ 70 Hz

 
 

Output
Voltage : 220/380 Vac; 230/400 Vac; 240/415 Vac (3-phase, 4-wire + G)
Voltage Harmonic Distortion : ≦ 0.5% (linear load)
Frequency : 50/60 Hz
Frequency Regulation : ±0.05 Hz (battery mode)
Overload Capability : ≦ 125% : 10 minutes; ≦ 150% : 1 minute

 
 

Display : 10” color touch screen

 
 

Interface
Standard
RS232 x 1, Parallel port x 2, USB x 3, RS485 x 1, Relay I/O card slot x 1, REPO x 1, Input dry contact x 4, Output dry contact x 6,
Battery temperature sensor x 4, External switch detection x 4, RJ45 x 1, Ethernet x 1
Optional : Relay I/O card, Battery cabinet temperature sensor cable

 
 

Conformance
Safety :CE, RCM
UPS Classification According to IEC 62040-3 : VFI-SS-111

 
 

Efficiency
AC-AC Mode : Up to 96.5%
ECO Mode : 99%

 
 

Battery
Nominal Voltage : ±240 Vdc
Charge Voltage : ±272 Vdc (adjustable from 204V to 312V)
Battery number configuration : 30 ~ 46pcs (default: 40pcs)

 
 

Environment
Operating Altitude : 1000 meters (without derating)
Operating Temperature : 0 ~ 40℃
Audible Noise : <70 dB
Relative Humidity : 0 ~ 95% (non-condensing)

 
 

Others
Parallel Redundancy and Expansion : Maximum 8 units
Remote Emergency Power Off : Yes
Battery Start : Yes

 
 

Physical
Dimensions (W x D x H) : 600 x 1100 x 1600 mm
Weight : HPH-160K : 339 kg / HPH-200K : 376 kg

 
 

* The power rating is adjustable from default 160kVA to 150kVA via touch panel.
** When input vTHD is less than 1%

All specifications are subject to change without prior notice.