NT Series, Three Phase, 20-500 kVA

Enterprise power customized for greatest reliability

The Ultron NT series is a three phase UPS featuring customized I/P-O/P ratings for various applications. With N+X parallel redundancy or expansion, it guarantees high availability and reliability for your critical loads.

The Ultron NT series offers continued seamless protection for your business even under 100% unbalanced loading conditions. Its economy mode improves efficiency by 4% to 7% and saves operating cost.

  1. Available from 20 to 4,000 kVA (8 x 500 kVA in parallel).
  2. Parallel redundancy without requiring extra hardware to increase reliability.
  3. Optional harmonic filter and 12-pulse rectifier.
  4. Redundant auxiliary power and control circuit ensures higher reliability.
  5. Inbuilt maintenance and static bypass switch.
  6. Multi-language LCD display and LED status indicators.
  7. RS232, RS485 and six programmable dry contact outputs.
  8. Compatible with generator installation and unbalanced loads.
  9. Optional external battery cabinet for longer backup time.
  10. Parallel expansion as your business grows and consequently saves initial investment.
  11. Wide input voltage range extends battery lifetime.
  12. Economy mode saves energy and operating cost.
  13. Common battery installation saves initial investment.

Specifications

Model

HPH-160K / HPH-200K

 
 

Power Rating
HPH-160K : 160kVA* / 150kW
HPH-200K : 200kVA / 200kW

 
 

Input
Nominal Voltage : 220/380 Vac, 230/400 Vac , 240/415 Vac (3-phase, 4-wire + G)
Voltage Range : 176 ~ 276Vac (full load)
Current Harmonic Distortion : ≦ 3% **
Frequency : 40 ~ 70 Hz

 
 

Output
Voltage : 220/380 Vac; 230/400 Vac; 240/415 Vac (3-phase, 4-wire + G)
Voltage Harmonic Distortion : ≦ 0.5% (linear load)
Frequency : 50/60 Hz
Frequency Regulation : ±0.05 Hz (battery mode)
Overload Capability : ≦ 125% : 10 minutes; ≦ 150% : 1 minute

 
 

Display : 10” color touch screen

 
 

Interface
Standard
RS232 x 1, Parallel port x 2, USB x 3, RS485 x 1, Relay I/O card slot x 1, REPO x 1, Input dry contact x 4, Output dry contact x 6,
Battery temperature sensor x 4, External switch detection x 4, RJ45 x 1, Ethernet x 1
Optional : Relay I/O card, Battery cabinet temperature sensor cable

 
 

Conformance
Safety :CE, RCM
UPS Classification According to IEC 62040-3 : VFI-SS-111

 
 

Efficiency
AC-AC Mode : Up to 96.5%
ECO Mode : 99%

 
 

Battery
Nominal Voltage : ±240 Vdc
Charge Voltage : ±272 Vdc (adjustable from 204V to 312V)
Battery number configuration : 30 ~ 46pcs (default: 40pcs)

 
 

Environment
Operating Altitude : 1000 meters (without derating)
Operating Temperature : 0 ~ 40℃
Audible Noise : <70 dB
Relative Humidity : 0 ~ 95% (non-condensing)

 
 

Others
Parallel Redundancy and Expansion : Maximum 8 units
Remote Emergency Power Off : Yes
Battery Start : Yes

 
 

Physical
Dimensions (W x D x H) : 600 x 1100 x 1600 mm
Weight : HPH-160K : 339 kg / HPH-200K : 376 kg

 
 

* The power rating is adjustable from default 160kVA to 150kVA via touch panel.
** When input vTHD is less than 1%

All specifications are subject to change without prior notice.NT-20K / NT-30K / NT-40K / NT-50K

NT-60K / NT-80K / NT-100K / NT-120K
NT-160K / NT-200K / NT-260K
NT-320K / NT-400K / NT-500K

Power Rating
NT-20K : 20kVA / 16kW
NT-30K : 30kVA / 24kW
NT-40K : 40kVA / 32kW
NT-50K : 50kVA / 40kW
NT-60K : 60kVA / 48kW
NT-80K : 80kVA / 64kW
NT-100K : 100kVA / 80kW
NT-120K : 120kVA / 96kW
NT-160K : 160kVA / 128kW
NT-200K : 200kVA / 160kW
NT-260K : 260kVA / 208kW
NT-320K : 320kVA / 256kW
NT-400K : 400kVA / 320kW
NT-500K : 500kVA / 400kW

Input
Nominal Voltage : 208/120; 380/220; 400/230; 415/240; 480/277 Vac (3 phase, 4-wire + G)
Voltage Range : 305~499 Vac
Current Harmonic Distortion : < 3% (with optional power filter, full load)

Frequency : 45~65Hz

Output

Voltage
208/120, 380/220, 400/230, 415/240, 480/277 Vac (3 phase, 4-wire + G)
220, 230, 240 Vac (1 phase, 2-wire + G)*
Output Power Factor : 0.8
Voltage Harmonic Distortion : ≤ 3% (linear load)
Voltage Regulation : ± 1% (static)
Frequency
50/60 Hz ± 0.01% (internal oscillator)
50/60 Hz ± 1% (synchronized)
Overload Capability
≤ 110%: 60 minutes
110 ~ 125%: 10 minutes
126 ~ 150%: 1 minute

Interface
Standard : RS232 x 1, RS485 x 2, SMART slot x 1, Output dry contact x 6

Other Features
Parallel Redundancy : Up to 8 units
Emergency Power Off : Local and remote
SRAM Event Log : 500 records
Input Harmonic Improvement : Optional harmonic filter and 12-pulse rectifier

Efficiency
AC-AC
NT-20K : 90%
NT-30K~40K : 91%
NT-50K~60K : 91.5%
NT-80K~100K : 92%
NT-120K~200K : 92.5%
NT-260K~500K : 93%
ECO Mode
NT-20K : > 97%
NT-30~500K : > 97.5%

Environment
Operating Temperature : 0 ~ 40ºC
Relative Humidity : 0 ~ 95% (non-condensing)
IP Protection : IP20
Audible Noise (at 1.5 meters)
NT-20K~40K : ≤ 60dB
NT-50K~120K : ≤ 65dB
NT-160K~200K : ≤ 68dB
NT-260K~400K : ≤ 72dB
NT-500K : ≤ 77dB

Physical-6pules
Dimensions(WxDxH) **
NT-20K~80K : 600 x 800 x 1400 mm
NT-100K~120K : 800 x 830 x 1700 mm
NT-160K~200K : 1200 x 830 x 1700 mm
NT-260K~400K : 1600 x 995 x 1950 mm
NT-500K : 1900* x 995 x 1950 mm

Weight
NT-20K : 365 kg
NT-30K : 365 kg
NT-40K : 425 kg
NT-50K : 460 kg
NT-60K : 506 kg
NT-80K : 525 kg
NT-100K : 700 kg
NT-120K : 745 kg
NT-160K : 1050 kg
NT-200K : 1085 kg
NT-260K : 1680 kg
NT-320K : 1720 kg
NT-400K : 1920 kg
NT-500K : 3110 kg*

* 500 kVA model is assembled into two cabinets: Inverter (width=1100 mm, 1760 kg) and Rectifier (width=800 mm, 1350 kg).